Deutsche Seite
Print View
 
 

ComBridge MCG

At the upper side of the casing the following connectors can be found (left to right):
  • LED -> Programming LED
  • Prog. -> Programming Button

On the device front the following elements can be found:

  • Display 2x12 chars
  • MOVE-button
  • Prg/Set-button
  • ESC-button
  • Operating-LED (PWR)
  • Failure-LED

At the lower side of the casing the following connectors can be found (left to right):

  • 24 VDC -> Power Supply Connector
  • RJ45 Connector for Ethernet
  • KNX Bus Connector
Display Elements: Red LED to indicate KNX Normal-/Addressing Mode
Green PWR-LED to signal device readiness (blinks when in normal operation mode)
Red ERR-LED to signal fault status
LC-Display, 2 lines with 12 characters each with menu for commissioning and setting of parameters
User Elements: Programming Button to toggle between normal and addressing mode
3 buttons (SCROLL, Prg/Set, ESC) on display front to commission the device and set parameters
Connectors: KNX bus connector
RJ45 Connector for Ethernet

Bus Coupler: integrated in device, connection with standard bus connector
Dimensions: 35mm DIN rail mounting 4 units wide:
Width: 70mm
Hight: 55mm
Lenght: 86mm
Weight: 160 g
Casing: LEXAN UL-94-V0
Environmental Conditions: EN 50090-2-2
  Operation: 0°C to +45°C
Storage: -25°C to +70°C
Rel. Humidity: non condensing: 5 % to 93 %
Power Supply: External or KNX Bus, SELV 24 VDC
Protection type: IP20 according to EN 60529, Din VDE 0470
Class: I according to IEC 1140
Pollution Class: 2
Overvoltage Category: III
EMC: complies with EN 50081-1, EN 50082-2, EN 50090-2-2
CE-Signage According to EMC-Guidelines (Residential and commercial buildings), Low Voltage guidelines
Certification EIB/KNX registered
©1996-2011 IPAS GmbH Duisburg